User Tools

Site Tools


en:blacky-install

Differences

This shows you the differences between two versions of the page.

Link to this comparison view

Both sides previous revisionPrevious revision
Next revision
Previous revision
Last revisionBoth sides next revision
en:blacky-install [2017/04/25 08:50] – [Peripherals description] arsien:blacky-install [2017/04/26 09:40] – [Peripherals description] arsi
Line 8: Line 8:
 {{ :sk:blackymax-connectors1.png?400|}} {{ :sk:blackymax-connectors1.png?400|}}
   - Jumper - RS485 terminator   - Jumper - RS485 terminator
-  - RS 485 connector+  - RS 485 [C-bus] connector
   - RS 232/MMI connector   - RS 232/MMI connector
   - Ethernet   - Ethernet
Line 16: Line 16:
   - Power supply 24V DC   - Power supply 24V DC
  
-=== RS 485 connector **[/dev/ttyO5]** ===+=== RS 485 connector ===
   - **Shielding**   - **Shielding**
   - **A+**   - **A+**
   - **B-**   - **B-**
   - **GND**   - **GND**
-=== RS 232 connector [/dev/ttyO2] ===+ 
 +{{ :en:konektor.png|}} 
 +=== RS 232 connector ===
   - **GND**   - **GND**
   - **MMI power**   - **MMI power**
Line 34: Line 36:
 ---- ----
 {{ :sk:blackymax-connectors2.png?400|}} {{ :sk:blackymax-connectors2.png?400|}}
-  - RS 232 DB9 [/dev/ttyO1]+  - RS 232 DB9 
   - USB Host   - USB Host
   - HDMI **Do not connect**   - HDMI **Do not connect**
Line 40: Line 42:
   - M-Bus   - M-Bus
  
-=== M-Bus connector [/dev/ttyO4] ===+=== M-Bus connector  ===
   - M-Bus   - M-Bus
   - M-Bus   - M-Bus
Line 47: Line 49:
 :!: In the event of prolonged short-circuit situation, converter will reduce output voltage. To restore converters function it is required to break converters power supply. :!: In the event of prolonged short-circuit situation, converter will reduce output voltage. To restore converters function it is required to break converters power supply.
 ---- ----
 +=== Linux  COM port names ===
 +
 +    RS485 - /dev/ttyO5
 +    M-Bus - /dev/ttyO4
 +    RS232 DB9 - /dev/ttyO1
 +    RS232 MMI - /dev/ttyO2
 +
 +----
 +
 ===== First run ===== ===== First run =====
 :!: From factory settings, converters IP address is set to **192.168.0.202**. You will be able to connect to converter by setting your IP address in range **192.168.0.XXX** with net mask set to **255.255.255.0** :!: From factory settings, converters IP address is set to **192.168.0.202**. You will be able to connect to converter by setting your IP address in range **192.168.0.XXX** with net mask set to **255.255.255.0**
en/blacky-install.txt · Last modified: 2018/02/23 22:29 by 127.0.0.1